Instrument Transformer FAT Checklist

2026-02-26 09:00:00
Instrument Transformer FAT Checklist

Instrument Transformer FAT Checklist

Instrument transformers are small compared with switchgear, but CT/VT mistakes propagate into metering and protection problems. A structured FAT verifies that CTs and VTs match your specification before shipping.

This checklist can be used as a practical FAT template for CT/VT procurement.

1) Nameplate and Specification Match

  • ratio and secondary rating (1A/5A for CT; secondary voltage for VT)
  • accuracy class (metering vs protection)
  • burden rating
  • insulation level and voltage class
  • terminal markings and polarity

2) Visual Inspection

  • housing integrity, cleanliness, and damage checks
  • terminal condition and labeling
  • mounting features and accessories included

3) Routine Electrical Tests (Per Standard)

  • insulation tests appropriate to rating
  • ratio verification
  • polarity checks (CT)
  • functional checks for multi-ratio taps (if applicable)

4) Documentation Package

  • test reports with serial number traceability
  • drawings or terminal diagrams
  • operation/installation instructions
  • packing list and spares list (if required)

Internal Links

CT products: Current Transformers.

VT products: Voltage Transformers.

Project inquiries: Contact Us.

Conclusion

A CT/VT FAT checklist reduces commissioning surprises. Verify nameplate fields, run routine tests aligned with the governing standard, and require traceable test reports. These steps protect both billing accuracy and protection reliability.