- Overview
- Recommended Products
Compared with the SCB10 product, the no-load loss is reduced by 12%.
The noise level is reduced, which greatly improves the economic benefits.
It has high mechanical strength, good short-circuit resistance, flame retardancy, explosion prevention, and no pollution. It can be directly installed on the load.
It is maintenance-free, has good moisture resistance, can operate under 100% humidity,does not require preheating treatment before commissioning, and does not require dehumidification treatment during intermittent operation.
It has a small external dimension, light weight, and low partial discharge.
It has a high insulation level and good resistance to lightning impulse.
It has strong heat dissipation ability and can operate at 150% of the rated load under the condition of cold air.
Enforce standars
GB 1094-2013 《Power transformer》
GB/T 2900.95 Electrical terms transformers, voltage regulator and reactors
GB/T 10228 Technical parameters and requirements of dry type powertransformers
GB 20052-2020 Power transformer energy efficiency limit value and energy
IEC 60076 《Power transformer》
Type description

Normal service condition
Below an altitude of 1000 meters
The highest ambient temperature is +40 degrees Celsius
The highest daily average temperature is +20 degrees Celsius
The lowest outdoor temperature is -20 degrees Celsius
Performance parameter
| Ratedcapacity(kVA) | Voltage group | SC(B)11 | Dimension(mm) | Weight(kg) | ||||||||
| HV(kV) | Taprange | LV(kV) | Impedancevoltage(%) | No-loadloss(W) | Load loss120℃(W) | No-loadcurrent(%) | Soundlevel(dB) | L | W | H | ||
| 30 | 101110.56.66.36 | ±2x2.5%±5% | 04 | 4 | 170 | 710 | 2.0 | 44 | 620 | 400 | 600 | 220 |
| 50 | 250 | 1000 | 2.0 | 44 | 650 | 400 | 740 | 320 | ||||
| 80 | 330 | 1380 | 1.5 | 45 | 750 | 500 | 770 | 460 | ||||
| 100 | 360 | 1570 | 1.5 | 45 | 800 | 500 | 830 | 580 | ||||
| 125 | 420 | 1850 | 1.3 | 46 | 950 | 880 | 1090 | 750 | ||||
| 160 | 490 | 2130 | 1.3 | 46 | 950 | 880 | 1090 | 780 | ||||
| 200 | 560 | 2530 | 1.1 | 47 | 1050 | 900 | 1200 | 850 | ||||
| 250 | 650 | 2760 | 1.1 | 48 | 1050 | 900 | 1200 | 1030 | ||||
| 315 | 790 | 3470 | 1.0 | 48 | 1080 | 900 | 1250 | 1060 | ||||
| 400 | 880 | 3990 | 1.0 | 49 | 1110 | 950 | 1270 | 1400 | ||||
| 500 | 1040 | 4880 | 1.0 | 49 | 1130 | 950 | 1380 | 1550 | ||||
| 630 | 1210 | 5880 | 0.85 | 49 | 1200 | 950 | 1450 | 1820 | ||||
| 630 | 6 | 1170 | 5960 | 0.85 | 50 | 1320 | 950 | 1375 | 1850 | |||
| 800 | 1370 | 6960 | 0.85 | 51 | 1310 | 1000 | 1315 | 2150 | ||||
| 1000 | 1590 | 8130 | 0.85 | 52 | 1400 | 1070 | 1520 | 2550 | ||||
| 1250 | 1880 | 9690 | 0.85 | 53 | 1440 | 1150 | 1570 | 3020 | ||||
| 1600 | 2210 | 11730 | 0.85 | 54 | 1650 | 1200 | 1795 | 4500 | ||||
| 2000 | 2750 | 14450 | 0.7 | 55 | 1800 | 1260 | 1870 | 5300 | ||||
| 2500 | 3240 | 17170 | 0.7 | 56 | 1950 | 1260 | 2035 | 6200 | ||||